8.4.3.1 To ensure that any evolved hydrogen is
expelled, battery compartments, lockers and containers should be exhausted
from the highest point of the space and air supplied at a level below
the top of the batteries.
8.4.3.2 If mechanical means are employed to ventilate
a battery compartment directly, then the components must not be a
potential source of ignition. Reference should be made to the requirements
of the ATEX Directive (EC Directive 94/9/EC concerned with equipment
and protective systems intended for use in potentially explosive atmospheres).