The nozzles should be installed to protect the cabin and
corridor in accordance with the manufacturer’s design and installation
instructions subject to the following:
-
.1 if only one ceiling nozzle is installed in
the cabin, it may not be placed in the shaded area in figure 2;
-
.2 if two or more ceiling nozzles are installed
in the cabin the nominal water flux density should be homogeneously
distributed throughout the cabin;
-
.3 corridor nozzles should not be placed closer
to the centreline of the cabin doorway than one half the maximum spacing
recommended by the manufacturer. An exception is systems where nozzles
are required to be placed outside each doorway; and
-
.4 cabin mounted sidewall nozzles should be installed
on the centreline of the front wall of the cabin adjacent to the doorway,
aimed towards the rear of the cabin.
Figure 2