6.6.1 Electrical equipment and wiring installed
in hazardous areas should be limited to that necessary for operational
purposes. Only the cables and types of equipment described in this
chapter may be installed.
6.6.2 Where, in the following, reference is made
to certified types of equipment, such equipment should be certified
as suitable for the flammable gas/air mixture which may be encountered.
6.6.3 Cables and types of electrical equipment
permitted in hazardous areas are as follows:
-
.1
Zone 0
Certified intrinsically safe circuits or equipment and associated
wiring.
-
.2
Zone 1
Certified increased safety
equipment; for increased safety motors, due consideration should be
given to the protection against overcurrent.
Through runs of cables.
-
.3
Zone 2
-
.3.1 Certified instrinsically safe circuits or
equipment and associated wiring.
-
.3.2 Certified flameproof (explosion proof) equipment.
-
.3.3 Certified increased safety equipment; for
increased safety motors, due consideration should be given to the
protection against overcurrent.
-
.3.4 Pressurized-enclosure type equipment which
is to the satisfaction of the Administration .
-
.3.5 Any equipment of a type which ensures absence
of sparks or arcs and of "hot spots" during normal operation and which
is to the satisfaction of the Administration .
-
.3.6 Through runs of cables.
6.6.4 Permanently installed, fixed cables passing
through zone 1 hazardous areas should be fitted with a conductive
covering, braiding or sheath for earth detection. Flexible cables
passing through such areas should be to the satisfaction of the Administration.