9.8.1 The drill floor should be protected by a fixed pressure water-spraying
system designed to provide a minimum water application rate of 20 l/m2/min to
the drill floor and related equipment, including emergency shutdown equipment, critical
structural components, and enclosure fire barriers. Alternatively, multiple fixed monitors
discharging at a minimum flow rate and pressure 1,900 l/min at 1 N/mm2 may be
provided and arranged such that all areas and equipment can be reached by at least two
monitors which are widely separated.
9.8.2 The system should be designed for manual release from release stations
located outside the protected area. Any section valves necessary for the operation of the
system should be located outside the protected area. Automatic release may be accepted by
the Administration.
9.8.3 Nozzles, piping, fittings and related components should be designed to
withstand exposure to temperatures up to 925°C.
9.8.4 The main fire pumps may be used to supply the fixed pressure
water-spraying system if they have sufficient capacity to simultaneously supply the fire
main at the required flow and pressure.