3.1 Alarm system requirements
3.1.1 Alarm systems should be type tested in accordance with IEC 60092-504, as
appropriate.
3.1.2 A switch for testing audible and visual alarms should be provided at the alarm
panel and the switch should return to the off position when not operated.
3.2 Alarm system testing requirements
The visual and audible alarms should be tested to demonstrate the
following:
-
.1 the visual indication may not be extinguished by the operator;
-
.2 they should be set at a level that alerts operators but does not
interfere with the safe operation of the ship; and
-
.3 they should be distinguishable from other alarms.
3.3 System test requirements
3.3.1 After installation, a functionality test should be carried out. The test should
represent the presence of water at the detectors for every level monitored. Simulation
methods may be used where the direct use of water is impracticable.
3.3.2 Each detector alarm should be tested to verify that the pre-alarm and main alarm
levels operate for every space where they are installed and indicate correctly. Also,
the fault monitoring arrangements should be tested as far as practicable.
3.3.3 Records of testing of alarm systems should be retained on board.