13.6.1 Gas detection equipment shall be installed
to monitor the integrity of the cargo containment, cargo handling
and ancillary systems, in accordance with this section.
13.6.2 A permanently installed system of gas detection
and audible and visual alarms shall be fitted in:
-
.1 all enclosed cargo and cargo machinery spaces
(including turrets compartments) containing gas piping, gas equipment
or gas consumers;
-
.2 other enclosed or semi-enclosed spaces where
cargo vapours may accumulate, including interbarrier spaces and hold
spaces for independent tanks other than type C tanks;
-
.3 airlocks;
-
.4 spaces in gas-fired internal combustion engines,
referred to in 16.7.3.3;
-
.5 ventilation hoods and gas ducts required by
chapter 16;
-
.6 cooling/heating circuits, as required by 7.8.4;
-
.7 inert gas generator supply headers; and
-
.8 motor rooms for cargo handling machinery.
13.6.3 Gas detection equipment shall be designed,
installed and tested in accordance with recognized standardsfootnote and shall be suitable for the cargoes to
be carried in accordance with column "f" in table of
chapter 19.
13.6.4 Where indicated by an "A" in column "f" in
the table of chapter 19 ships certified for carriage of non-flammable products, oxygen
deficiency monitoring shall be fitted in cargo machinery spaces and hold spaces for
independent tanks other than type C tanks. Furthermore, oxygen deficiency monitoring
equipment shall be installed in enclosed or semi-enclosed spaces containing equipment
that may cause an oxygen-deficient environment such as nitrogen generators, inert gas
generators or nitrogen cycle refrigerant systems.
13.6.5 In the case of toxic products or both toxic
and flammable products, except when column "i" in the
table of chapter 19 refers to 17.5.3, portable equipment can be used
for the detection of toxic products as an alternative to a permanently
installed system. This equipment shall be used prior to personnel
entering the spaces listed in 13.6.2 and at 30-minute intervals while
they remain in the space.
13.6.6 In the case of gases classified as toxic
products, hold spaces and interbarrier spaces shall be provided with
a permanently installed piping system for obtaining gas samples from
the spaces. Gas from these spaces shall be sampled and analysed from
each sampling head location.
13.6.7 Permanently installed gas detection shall
be of the continuous detection type, capable of immediate response.
Where not used to activate safety shutdown functions required by 13.6.9
and chapter 16, sampling type detection may be accepted.
13.6.8 When sampling type gas detection equipment
is used, the following requirements shall be met:
-
.1 the gas detection equipment shall be capable
of sampling and analysing for each sampling head location sequentially
at intervals not exceeding 30 min;
-
.2 individual sampling lines from sampling heads
to the detection equipment shall be fitted; and
-
.3 pipe runs from sampling heads shall not be
led through non-hazardous spaces except as permitted by 13.6.9.
13.6.9 The gas detection equipment may be located
in a non-hazardous space, provided that the detection equipment such
as sample piping, sample pumps, solenoids and analysing units are
located in a fully enclosed steel cabinet with the door sealed by
a gasket. The atmosphere within the enclosure shall be continuously
monitored. At gas concentrations above 30% lower flammable limit (LFL)
inside the enclosure, the gas detection equipment shall be automatically
shut down.
13.6.10 Where the enclosure cannot be arranged
directly on the forward bulkhead, sample pipes shall be of steel or
equivalent material and be routed on their shortest way. Detachable
connections, except for the connection points for isolating valves
required in 13.6.11 and analysing units, are not permitted.
13.6.11 When gas sampling equipment is located
in a non-hazardous space, a flame arrester and a manual isolating
valve shall be fitted in each of the gas sampling lines. The isolating
valve shall be fitted on the non-hazardous side. Bulkhead penetrations
of sample pipes between hazardous and non-hazardous areas shall maintain
the integrity of the division penetrated. The exhaust gas shall be
discharged to the open air in a non-hazardous area.
13.6.12 In every installation, the number and
the positions of detection heads shall be determined with due regard
to the size and layout of the compartment, the compositions and densities
of the products intended to be carried and the dilution from compartment
purging or ventilation and stagnant areas.
13.6.13 Any alarms status within a gas detection
system required by this section shall initiate an audible and visible
alarm:
-
.1 on the navigation bridge;
-
.2 at the relevant control station(s) where continuous
monitoring of the gas levels is recorded; and
-
.3 at the gas detector readout location.
13.6.14 In the case of flammable products, the
gas detection equipment provided for hold spaces and interbarrier
spaces that are required to be inerted shall be capable of measuring
gas concentrations of 0% to 100% by volume.
13.6.15 Alarms shall be activated when the vapour
concentration by volume reaches the equivalent of 30% LFL in air.
13.6.16 For membrane containment systems, the
primary and secondary insulation spaces shall be able to be inerted
and their gas content analysed individuallyfootnote. The alarm in the secondary insulation
space shall be set in accordance with 13.6.15, that in the primary
space is set at a value approved by the Administration or recognized
organization acting on its behalf.
13.6.17 For other spaces described by 13.6.2,
alarms shall be activated when the vapour concentration reaches 30%
LFL and safety functions required by chapter 16 shall be activated
before the vapour concentration reaches 60% LFL. The crankcases of
internal combustion engines that can run on gas shall be arranged
to alarm before 100% LFL.
13.6.18 Gas detection equipment shall be so designed
that it may readily be tested. Testing and calibration shall be carried
out at regular intervals. Suitable equipment for this purpose shall
be carried on board and be used in accordance with the manufacturer's
recommendations. Permanent connections for such test equipment shall
be fitted.
13.6.19 Every ship shall be provided with at least
two sets of portable gas detection equipment that meet the requirement
of 13.6.3 or an acceptable national or international standard.
13.6.20 A suitable instrument for the measurement
of oxygen levels in inert atmospheres shall be provided.