17.16.1 Methyl acetylene-propadiene mixtures shall
be suitably stabilized for transport. Additionally, upper limits of
temperatures and pressure during the refrigeration shall be specified
for the mixtures.
17.16.2 Examples of acceptable stabilized compositions
are:
-
.1 Composition 1:
-
.1 maximum methyl acetylene to propadiene molar
ratio of 3 to 1;
-
.2 maximum combined concentration of methyl acetylene
and propadiene of 65 mol%;
-
.3 minimum combined concentration of propane,
butane, and isobutane of 24 mol%, of which at least one third (on
a molar basis) shall be butanes and one third propane;
-
.4 maximum combined concentration of propylene
and butadiene of 10 mol%;
-
.2 Composition 2:
-
.1 maximum methyl acetylene and propadiene combined
concentration of 30 mol%;
-
.2 maximum methyl acetylene concentration of 20
mol%;
-
.3 maximum propadiene concentration of 20 mol%;
-
.4 maximum propylene concentration of 45 mol%;
-
.5 maximum butadiene and butylenes combined concentration
of 2 mol%;
-
.6 minimum saturated C4 hydrocarbon concentration
of 4 mol%; and
-
.7 minimum propane concentration of 25 mol%.
17.16.3 Other compositions may be accepted, provided
the stability of the mixture is demonstrated to the satisfaction of
the Administration.
17.16.4 If a ship has a direct vapour compression
refrigeration system, this shall comply with the following requirements,
subject to pressure and temperature limitations depending on the composition.
For the example compositions given in 17.16.2, the following features
shall be provided:
-
.1 a vapour compressor that does not raise the
temperature and pressure of the vapour above 60°C and 1.75 MPa
gauge during its operation, and that does not allow vapour to stagnate
in the compressor while it continues to run;
-
.2 discharge piping from each compressor stage
or each cylinder in the same stage of a reciprocating compressor shall
have:
-
.1 two temperature-actuated shutdown switches
set to operate at 60°C or less;
-
.2 a pressure-actuated shutdown switch set to
operate at 1.75 MPa gauge or less; and
-
.3 a safety relief valve set to relieve at 1.8
MPa gauge or less;
-
.3 the relief valve required by .2.3 shall vent
to a mast meeting the requirements of 8.2.10, 8.2.11 and 8.2.15 and
shall not relieve into the compressor suction line; and
-
.4 an alarm that sounds in the cargo control position
and in the navigation bridge when a high-pressure switch, or a high-temperature
switch, operates.
17.16.5 The piping system, including the cargo
refrigeration system, for tanks to be loaded with methyl acetylene-propadiene
mixtures shall be either independent (as defined in 1.2.28) or separate
(as defined in 1.2.47) from piping and refrigeration systems for other
tanks. This segregation shall apply to all liquid and vapour vent
lines and any other possible connections, such as common inert gas
supply lines.