4.5.1 When tested in accordance with 5.5, the nozzle should open and,
within 5 s after the release of the heat responsive element, should
operate satisfactorily by complying with the requirements of 5.10. Any lodgement of released
parts should be cleared within 60 s of release for standard response
heat responsive elements and within 10 s of release for fast and special
response heat responsive elements or the nozzle should then comply
with the requirement of 5.11.
4.5.2 The nozzle discharge components should not
sustain significant damage as a result of the functional test specified
in 5.5.6 and should have
the same flow constant range and water droplet size and velocity within