Purpose
(1) The purpose of this part is to contain a fire in the space of origin
by meeting the following functional requirements-
-
(a) the ship shall be subdivided by thermal and
structural boundaries;
-
(b) thermal insulation of boundaries shall have due
regard to the fire risk of the space and adjacent
spaces;
-
(c) the fire integrity of the divisions shall be
maintained at openings and penetrations; and
-
(d) for the purposes of Chapter 6 of the Code in
general and for section 6.7 (Containment of Fire)
in particular, rooms and spaces containing
furniture and furnishings of restricted fire risk
which form part of an escape route are those rooms
and spaces (whether cabins, public spaces, offices
or other types of accommodation) in which-
-
(i) case furniture such as desks, wardrobes,
dressing tables, bureaux, or dressers, are
constructed entirely of approved non-combustible
materials, except that a combustible veneer not
exceeding 2 mm may be used on the working surface
of such articles;
-
(ii) free-standing furniture such as chairs,
sofas, or tables, are constructed with frames of
non-combustible materials;
-
(iii) draperies, curtains and
other suspended textile materials have qualities
of resistance to the propagation of flame not
inferior to those of wool having a mass of 0.8
kg/m2 , this being
determined in accordance with the Fire Test
Procedures Code;
-
(iv) floor coverings have low flame-spread
characteristics;
-
(v) exposed surfaces of bulkheads, linings
and ceilings have low flame-spread
characteristics;
-
(vi) upholstered furniture has qualities of
resistance to the ignition and propagation of
flame, this being determined in accordance with
the Fire Test Procedures Code; and
-
(vii) bedding components have qualities of
resistance to the ignition and propagation of
flame, this being determined in accordance with
the Fire Test Procedures Code.
Thermal and Structural Subdivision
(2) Ships shall be subdivided into spaces by thermal and structural
divisions having regard to the fire risks of the spaces.
Main Vertical Zones and Horizontal Zones
(3) The hull, superstructure and deckhouses in way of accommodation and
service spaces shall be subdivided into main vertical zones by "A"
class divisions and these divisions shall have insulation values in
accordance with Tables 6.1 and 6.2.
(4) The main vertical zones shall comply with the following provisions-
-
(a) the bulkheads forming the boundaries of the main
vertical zones above the bulkhead deck shall as far
as practicable, be in line with watertight
subdivision bulkheads situated immediately below the
bulkhead deck;
-
(b) the length and width of main vertical
zones may be extended to a maximum of 48 metres in
order to bring the ends of main vertical zones to
coincide with watertight subdivision bulkheads or in
order to accommodate a large public space extending
for the whole length of the main vertical zone
provided that the total area of the main vertical
zone is not greater than 1,600 m2 on any
deck;
-
(c) the length or width of a main vertical zone shall be
the maximum distance between the furthermost points
of the bulkheads bounding it; and
-
(d) main vertical zones may be stepped or may consist of
one or more horizontal zones where it is
impracticable from structural or design
considerations to achieve compliance otherwise; in
all cases however the Administration shall be
satisfied that an equivalent level of safety and
protection is achieved.
(5) Bulkheads forming the boundaries of main vertical zones shall extend
from deck to deck and to the shell or other boundaries.
(6) Where a main vertical zone is subdivided by horizontal "A" class
divisions into horizontal zones for the purpose of providing an
appropriate barrier between a zone with sprinklers and a zone
without sprinklers, the divisions shall extend between adjacent main
vertical zone bulkheads and to the shell or exterior boundaries of
the ship and shall be insulated in accordance with the fire
insulation and integrity values given in Table 6.2.
Bulkheads within a Main Vertical Zone
(7) Bulkheads within accommodation and service spaces shall meet the
requirements of paragraphs (a) to (d) as appropriate taking
into consideration guidelines developed buy the
Organizationfootnote-
-
(a) Subject to paragraphs (a) and (b), bulkheads within
accommodation and service spaces which are not
required to be "A" class divisions shall be at least
"B" class or "C" class divisions as prescribed in
Tables 6.1 and 6.2; in addition, corridor bulkheads,
where not required to be "A" class, shall be "B"
class divisions which shall extend from deck to
deck;
-
(b) where continuous "B" class ceilings or linings are
fitted on both sides of the bulkhead, the portion of
the bulkhead behind the continuous ceiling or lining
shall be of material which, in thickness and
composition, is acceptable in the construction of
"B" class divisions, but which shall be required to
meet "B" class integrity standards only in so far as
is reasonable and practicable in the opinion of the
Administration;
-
(c) where, as will normally be the case, the ship is
protected by an automatic sprinkler system complying
with the provisions of the Fire Safety Systems Code, the
corridor bulkheads may terminate at a ceiling in the
corridor provided such bulkheads and ceilings are of
"B" class standard in compliance with subsections
(10) and (11): provided that all doors and frames in
such bulkheads shall be of non-combustible materials
and shall have the same fire integrity as the
bulkhead in which they are fitted.
-
(d) where “C” class divisions between similar purposed
spaces are provided (sleeping/washing/dressing),
these divisions do not need to be continuous and
the group of spaces may be considered as one.
(8) Bulkheads required to be "B" class divisions, except corridor
bulkheads as prescribed in subsection 6.9(2), shall extend from deck
to deck and to the shell or other boundaries; provided that where a
continuous "B" class ceiling or lining is fitted on both sides of a
bulkhead which is at least of the same fire resistance as the
adjoining bulkhead, the bulkhead may terminate at the continuous
ceiling or lining.
Fire Integrity of Bulkheads and Decks
(9) In addition to complying with the specific provisions for fire
integrity of bulkheads and decks, the minimum fire integrity of
bulkheads and decks shall be as prescribed in Tables 6.1 and 6.2.
(10) The following requirements shall govern application of the Tables-
-
(a) Tables 6.1 and 6.2 shall apply respectively to the
bulkheads and decks separating adjacent spaces;
-
(b) For determining the appropriate fire integrity
standards to be applied to divisions between
adjacent spaces-
-
(i) such spaces are classified according to
their fire risk as shown in sub paragraphs
(ba) to (bk) below;
-
(ii) where the contents and use of a space are
such that there is a doubt as to its
classification for the purpose of this paragraph ,
or where it is possible to assign two or more
classifications to a space, it shall be treated as
a space within the relevant category having the
most stringent boundary requirements;
-
(iii) smaller, enclosed rooms within a space
that have less than 30% communicating openings to
that space are considered separate spaces;
-
(iv) the fire integrity of the boundary
bulkheads and decks of such smaller rooms shall be
as prescribed in Tables 6.1 and 6.2;
-
(v) the title of each category is intended to
be typical rather than restrictive; and
-
(vi) the number in parentheses following each
category refers to the applicable column or row in
the Tables,
-
(ba) control stations (1):
spaces containing emergency sources of power
and lighting; wheelhouse and chartroom; spaces
containing the ship's radio equipment; fire
control stations; control room for propulsion
machinery when located outside the machinery
space; spaces containing centralised fire alarm
equipment;
-
(bb) corridors: (2):
passenger and crew corridors and lobbies;
-
(bc) accommodation spaces (3):
spaces as defined in section 1.3 excluding
corridors;
-
(bd) stairways: (4)
interior stairways; lifts; totally enclosed
emergency escape trunks and escalators (other than
those wholly contained within the machinery
spaces) and enclosures thereto (in this
connection, a stairway which is enclosed only at
one level shall be regarded as part of the space
from which it is not separated by a fire door);
-
(be) service spaces (low risk)
(5):
lockers and store-rooms not having
provisions for the storage of flammable liquids
and having areas less than 4m2 and
drying rooms and laundries;
-
(bf) machinery spaces of Category
A (6):
spaces as defined in section 1.3;
-
(bg) other machinery spaces (7):
electrical equipment rooms (auto-telephone
exchange, air-conditioning duct spaces); spaces as
defined in section 1.3 excluding machinery spaces
of category A;
-
(bh) service spaces (high risk)
(9):
galleys; pantries containing
cooking appliances; paint lockers; lockers and
store-rooms having areas of 4m2 or
more; spaces for the storage of flammable liquids;
saunas and workshops other than those forming part
of the machinery spaces;
-
(bi) open decks (10):
open deck spaces and enclosed promenades having
little or no fire risk; enclosed promenades shall
have no significant fire risk, meaning that
furnishing shall be restricted to deck furniture;
in addition, such spaces shall be naturally
ventilated by permanent openings; air spaces (the
space outside superstructures and deckhouses); and
-
(bj) garage spaces (11):
spaces as defined in section 1.3.
-
(bk) Evacuation stations and
external escape routes (12): Survival craft
stowage area; Open deck spaces and enclosed
promenades forming lifeboat and liferaft
embarkation and lowering stations; Assembly
stations, internal and external; External stairs
and open decks used for escape routes; The ship’s
side to the waterline in the lightest seagoing
condition, superstructure and deckhouse sides
situated below and adjacent to the liferaft and
evacuation slide embarkation areas
(11) In determining the applicable fire integrity standard of a boundary
between two spaces within a main vertical zone or horizontal zone
which is not protected by an automatic sprinkler system complying
with the provisions of the Fire Safety Systems Code or between such
zones neither of which is so protected, the higher of the two values
given in the tables shall apply.
(12) In determining the applicable fire integrity standard of a boundary
between two spaces within a main vertical zone or horizontal zone
which is protected by an automatic sprinkler system complying with
the provisions of the Fire Safety Systems Code or between such zones
both of which are so protected, the lesser of the two values given
in the tables shall apply and where a zone with sprinklers and a
zone without sprinklers meet within accommodation and service
spaces, the higher of the two values given in the tables shall apply
to the division between the zones.
(13) Continuous "B" class ceilings or linings, in association with the
relevant decks or bulkheads, may be accepted as contributing, wholly
or in part, to the required insulation and integrity of a division.
(14) External boundaries which are required in subsection 6.9(2) to be of
steel or other equivalent material may be pierced for the fitting of
windows and sidescuttles provided that there is no requirement for
such boundaries to have "A" class integrity. Similarly, in such
boundaries which are not required to have "A" class integrity, doors
may be constructed of materials which are to the satisfaction of the
Administration.
Construction and Arrangement of Saunas
(15) The perimeter of the sauna shall be of "A" class boundaries and may
include changing rooms, showers and toilets and the sauna shall be
insulated to "A-60" standard against other spaces except those
inside of the perimeter of the sauna and spaces of category (5), (7)
and (10).
(16) Bathrooms with direct access to saunas may be considered as part of
them. In such cases, the door between sauna and the bathroom need
not comply with fire safety requirements.
(17) The traditional wooden lining on the bulkheads and ceiling are
permitted in the sauna provided that-
-
(a) the ceiling above the oven shall be lined with a
non-combustible plate with an air gap of at least 30
millimetres; and
-
(b) the distance from the hot surfaces to combustible
materials shall be at least 500 millimetres or the
combustible materials shall be protected (e.g.,
non-combustible plate with an air gap of at least 30
millimetres).
(18) The traditional wooden benches are permitted to be used in the
sauna.
(19) The sauna door shall open outwards by pushing.
(20) Electrically heated ovens shall be provided with a timer.
Protection of Stairways and Lifts in Accommodation Area
(21) Stairways shall be within enclosures formed of "A" class divisions,
with positive means of closure at all openings, except that-
-
(a) a stairway connecting only two decks need not be
enclosed, provided the integrity of the deck is
maintained by proper bulkheads or self-closing doors
in one 'tween-deck space; when a stairway is closed
in one 'tween-deck space, the stairway enclosure
shall be protected in accordance with the table for
decks Tables 6.2; and
-
(b) Stairways may be fitted in the open in a public
space, provided they lie wholly within the public
space.
(22) Lift trunks shall be so fitted as to prevent the passage of smoke
and flame from one deck to another and shall be provided with means
of closing so as to permit the control of draught and smoke.
(23) Machinery for lifts located within stairway enclosures shall be
arranged in a separate room, surrounded by steel boundaries,
provided that small passages for lift cables are permitted.
(24) Lifts which open into spaces other than corridors, public spaces,
special category spaces, stairways and external areas shall not open
into stairways included in the means of escape.
(25) Non-load bearing partial bulkheads which separate adjacent cabin
balconies shall be capable of being opened by the crew from each
side for the purpose of fighting fires.
Protection of Atriums:
(26) Atriums shall be within enclosures formed of “A” class divisions
having a fire rating determined in accordance with Table 6.1.
(27) Decks separating spaces within atriums shall have a fire rating
determined in accordance with Table 6.2.
Table 6.1 - Fire Integrity of Bulkheads separating Adjacent
Spaces
Spaces
|
SOLAS Ref. No.
|
(1)
|
(2)
|
(3)
|
(4)
|
(5)
|
(6)
|
(7)
|
(9)
|
(10)
|
(11)
|
(12)
|
▼
|
►
|
Control stations
|
(1)
|
A-0c
|
A-0
|
A-60
|
A-0
|
A-15
|
A-60
|
A-15
|
A-60
|
*
|
A-60
|
A-0
|
Corridors
|
(2)
|
|
Ce
|
B-0e
|
A-0a
B-0e
|
B-0e
|
A-60
|
A-0
|
A-15
A-0d
|
*
|
A-30
|
A-60
|
Accommodation spaces
|
(3)
|
|
|
Ce
|
A-0a
B-0e
|
B-0e
|
A-60
|
A-0
|
A-15
A-0d
|
*
|
A-30
A-0d
|
A-60gh
|
Stairways
|
(4)
|
|
|
|
A-0a
B-0e
|
A-0a
B-0e
|
A-60
|
A-0
|
A-15
A-0d
|
*
|
A-30
|
A-0
|
Service spaces (low risk)
|
(5)
|
|
|
|
|
Ce
|
A-60
|
A-0
|
A-0
|
*
|
A-0
|
A-60b
|
Machinery spaces of Category A
|
(6)
|
|
|
|
|
|
*
|
A-0
|
A-60
|
*
|
A-60
|
A-60b
|
Other machinery spaces
|
(7)
|
|
|
|
|
|
|
A-0b
|
A-0
|
*
|
A-0
|
A-0
|
Service spaces (high risk)
|
(9)
|
|
|
|
|
|
|
|
A-0b
|
*
|
A-30
|
A-60b
|
Open decks
|
(10)
|
|
|
|
|
|
|
|
|
*
|
A-0
|
A-0
|
Garage spaces
|
(11)
|
|
|
|
|
|
|
|
|
|
A-30
|
A-60g
|
Evacuation stations and external escape
routes
|
(12)
|
|
|
|
|
|
|
|
|
|
|
|
Table 6.2 - Fire Integrity of Decks separating Adjacent
Spaces
Spaces
Below
▼
|
Spaces Above
►
|
(1)
|
(2)
|
(3)
|
(4)
|
(5)
|
(6)
|
(7)
|
(9)
|
(10)
|
(11)
|
(12)
|
Control stations
|
(1)
|
A-0
|
A-0
|
A-0
|
A-0
|
A-0
|
A-60
|
A-0
|
A-0
|
*
|
A-60
|
A-0
|
Corridors
|
(2)
|
A-0
|
*
|
*
|
A-0
|
*
|
A-60
|
A-0
|
A-0
|
*
|
A-30
|
A-60
|
Accommodation spaces
|
(3)
|
A-60
|
A-0
|
*
|
A-0
|
*
|
A-60
|
A-0
|
A-0
|
*
|
A-30
A-0d
|
A-60
|
Stairways
|
(4)
|
A-0
|
A-0
|
A-0
|
*
|
A-0
|
A-60
|
A-0
|
A-0
|
*
|
A-30
|
A-0
|
Service spaces (low risk)
|
(5)
|
A-15
|
A-0
|
A-0
|
A-0
|
*
|
A-60
|
A-0
|
A-0
|
*
|
A-0
|
A-60
|
Machinery spaces of Category A
|
(6)
|
A-60
|
A-60
|
A-60
|
A-60
|
A-60
|
*
|
A-60f
|
A-60
|
*
|
A-60
|
A-60
|
Other machinery spaces
|
(7)
|
A-15
|
A-0
|
A-0
|
A-0
|
A-0
|
A-0
|
*
|
A-0
|
*
|
A-0
|
A-60
|
Service spaces (high risk)
|
(9)
|
A-60
|
A-30
A-0d
|
A-30
A-0d
|
A-30
A-0d
|
A-0
|
A-60
|
A-0
|
A-0
|
*
|
A-30
|
A-60
|
Open decks
|
(10)
|
*
|
*
|
*
|
*
|
*
|
*
|
*
|
*
|
---
|
A-0
|
A-0
|
Garage spaces
|
(11)
|
A-60
|
A-30
|
A-30
A-0d
|
A-30
|
A-0
|
A-60
|
A-0
|
A-30
|
A-0
|
A-30
|
A-60
|
Evacuation stations and external escape
routes
|
(12)
|
A-0
|
A-0
|
A-0
|
A-0
|
A-0
|
A-0
|
A-0
|
A-0
|
---
|
A-0
|
A-0
|
Notes: To be applied to both tables 6.1 and 6.2 as appropriate
(For clarification as to which applies, see subsections (7)
& (8) and subsections (21) and (24))
a For clarification as to which applies, see paragraphs 6.7(7)
& (8) and 6.7(21) to (25)
b
Where spaces are of the same numerical category and superscript
"b" appears, a bulkhead or deck of the rating shown in the tables is
only required when the adjacent spaces are for a different purpose
(e.g., in category (9)). A galley next to a galley does not require
a bulkhead, but a galley next to a paint room requires an "A-0"
bulkhead.
c
Bulkheads separating the wheelhouse and chartroom from each
other may have a "B-0" rating. No fire rating is required for those
partitions separating the navigation bridge and the safety centre
when the latter is within the navigation bridge.
d
See subsections (11) and (12).
e
For the application of subsection (3), "B-0" and "C", where
appearing in Table 6.1, shall be read as "A-0".
f
Fire insulation need not be fitted if the machinery space in
category (7), in the opinion of the Administration, has little or no
fire risk.
g The ship’s side, to the waterline in the lightest seagoing
condition, superstructure and deckhouse sides situated below and
adjacent to liferafts and evacuation slides may be reduced to
"A-30".
h Where spaces of categories (6), (7), (8) and
(9) are located completely within the outer perimeter of the
assembly station, the bulkheads of these spaces are allowed to be of
"B-0" class integrity. Control positions for audio, video and light
installations may be considered as part of the assembly station.
* Where an asterisk appears in the Tables it
indicates that-
-
(a) the division is required to be of steel or other
equivalent material, but is not required to be of
"A" class standard subject to (e) below; however,
where a deck, except in a category (10) space, is
penetrated for the passage of electric cables, pipes
and vent ducts, such penetrations shall be made
tight to prevent the passage of flame and smoke;
-
(b) divisions between control stations (emergency
generators) and open decks may have air intake
openings without means for closure; unless a fixed
gas fire-extinguishing system is fitted in the
control station;
-
(c) for the application of subsection 6.7(3), in Table
6.2, “A” class divisions shall be read as "A-0",
except for category (10);
-
(d) for windows and doors, subsection 6.7(46) shall
apply; and
-
(e) boundaries facing life-saving appliances (except
those leading from stairways), embarkation and
assembly stations, external stairs and open decks
used for escape routes, and situated below survival
craft, liferaft and escape slide embarkation areas
shall have the same fire integrity as a window or
door as per subsection 6.7(46)(a) to (d).
Penetrations in Fire-Resisting Divisions and Prevention of Heat
Transmission
(28) Where "A" class divisions are penetrated, such penetrations shall
comply with the following provisions-
-
(a) subject to the provisions of subsection (36), the
penetrations shall be tested in accordance with the
Fire Test Procedures Code;
-
(b) in the case of ventilation ducts, subsections (57),
(61) and (62) shall apply;
-
(c) where a pipe penetration is made of steel or
equivalent material having a thickness of 3
millimetres or greater and a length of not less than
900 millimetres (preferably 450 millimetres on each
side of the division), and there are no openings,
testing is not required but such penetrations shall
be suitably insulated by extension of the insulation
at the same level of the division being penetrated.
(29) Where "B" class divisions are penetrated for the passage of electric
cables, pipes, trunks, ducts, etc., or for the fitting of
ventilation terminals, lighting fixtures and similar devices, such
penetrations shall comply with the following provisions-
-
(a) subject to the provisions of subsection (70),
arrangements shall be made to ensure that the fire
resistance is not impaired;
-
(b) pipes other than steel or copper that shall be
protected by either-
-
(i) a fire-tested penetration device suitable
for the fire resistance of the division pierced
and the type of pipe used; or
-
(ii) a steel sleeve, having a thickness of not
less than 1.8 millimetres and a length of not less
than 900 millimetres for pipe diameters of 150
millimetres or more and not less than 600
millimetres for pipe diameters of less than 150
millimetres (preferably equally divided to each
side of the division). The pipe shall be connected
to the ends of the sleeve by flanges or couplings;
or the clearance between the sleeve and the pipe
shall not exceed 2.5 millimetres; or any clearance
between pipe and sleeve shall be made tight by
means of non-combustible or other suitable
material.
(30) Uninsulated metallic pipes penetrating "A" or "B" class divisions
shall be of materials having a melting temperature which exceeds
950°C for "A-0" and 850°C for "B-0" class divisions.
(31) In approving structural fire protection details, the Administration
shall have regard to the risk of heat transmission at intersections
and terminal points of required thermal barriers. The insulation of
a deck or bulkhead shall be carried past the penetration,
intersection or terminal point for a distance of at least 450
millimetres in the case of steel and aluminium structures. If a
space is divided with a deck or a bulkhead of "A" class standard
having insulation of different values, the insulation with the
higher value shall continue on the deck or bulkhead with the
insulation of the lesser value for a distance of at least 450
millimetres.
Protection of Openings in Fire-Resisting Divisions
(32) Openings shall be provided with permanently attached means of
closing which shall be at least as effective for resisting fires as
the divisions in which they are fitted.
(33) The construction of doors and door frames in "A" class divisions,
with the means of securing them when closed, shall comply with the
following provisions-
-
(a) the construction shall provide resistance to fire as
well as to the passage of smoke and flame equivalent
to that of the bulkheads in which the doors are
situated, this being determined in accordance with
the Fire Test Procedures Code;
-
(b) doors and door frames shall be constructed of steel
or other equivalent material (for glass doors refer
to 2.12(22));
-
(c) steel watertight doors need not be insulated;
-
(d) doors approved without the sill being part of the
frame, shall be installed such that the gap under
the door does not exceed 12 mm;
-
(e) a non-combustible sill shall be installed under the
door such that floor coverings do not extend beneath
the closed door.
(34) It shall be possible for each door to be opened and closed from each
side of the bulkhead by one person only.
(35) Fire doors in main vertical zone bulkheads, galley boundaries and
stairway enclosures other than power-operated watertight doors and
those which are normally locked shall satisfy the following
requirements:
-
(a) the doors shall be self-closing and be capable of
closing with an angle of inclination of up to 3.5°
opposing closure;
-
(b) the approximate time of closure for hinged fire doors
shall be no more than 40s and no less than 10
seconds from the beginning of their movement with
the ship in upright position. The approximate
uniform rate of closure for sliding doors shall be
of no more than 0.2 m/s and no less than 0.1 m/s
with the ship in upright position;
-
(c) the doors, except those for emergency escape trunks,
shall be capable of remote release from the
continuously manned central control station, either
simultaneously or in groups, and shall be capable of
release also individually from a position at both
sides of the door. Release switches shall have an
on-off function to prevent automatic resetting of
the system;
-
(d) hold-back hooks not subject to central control
station release are prohibited;
-
(e) a door closed remotely from the central control
station shall be capable of being re-opened from
both sides of the door by local control. After such
local opening, the door shall automatically close
again;
-
(f) indication shall be provided at the fire door
indicator panel in the continuously manned central
control station whether each door is closed;
-
(g) the release mechanism shall be so designed that the
door will automatically close in the event of
disruption of the control system or central power
supply;
-
(h) local power accumulators for power-operated doors
shall be provided in the immediate vicinity of the
doors to enable the doors to be operated at least
ten times (fully opened and closed) after disruption
of the control system or central power supply using
the local controls;
-
(i) disruption of the control system or central power
supply at one door shall not impair the safe
functioning of the other doors;
-
(j) remote-released sliding or power-operated doors shall
be equipped with an alarm that sounds at least 5
seconds but no more than 10 seconds, after the door
is released from the central control station and
before the door begins to move and continues
sounding until the door is completely closed;
-
(k) a door designed to re-open upon contacting an object
in its path shall re-open not more than 1 metre from
the point of contact;
-
(l) double-leaf doors equipped with a latch necessary for
their fire integrity shall have a latch that is
automatically activated by the operation of the
doors when released by the system;
-
(m) the components of the local control system shall be
accessible for maintenance and adjusting;
-
(n) power-operated doors shall be provided with a control
system of an approved type which shall be able to
operate in case of fire and be in accordance with
the Fire Test Procedures Code. This system shall
satisfy the following requirements-
-
(i) the control system shall be able to operate
the door at the temperature of at least 200°C for
at least 60 min, served by the power supply;
-
(ii) the power for all other doors not subject
to fire shall not be impaired; and
-
(iii) at temperatures exceeding 200°C, the
control system shall be automatically isolated
from the power supply and shall be capable of
keeping the door closed up to at least 945°C.
(36) Where a space is protected by an automatic sprinkler fire detection
and fire alarm system complying with the provisions of the Fire
Safety Systems Code or fitted with a continuous "B" class ceiling,
openings in decks not forming steps in main vertical zones nor
bounding horizontal zones shall be closed reasonably tight and such
decks shall meet the "A" class integrity requirements in so far as
is reasonable and practicable in the opinion of the Administration.
(37) The requirements for "A" class integrity of the outer boundaries of
a ship shall not apply to-
-
(a) glass partitions, windows and sidescuttles, provided
that there is no requirement for such boundaries to
have "A" class integrity in subsection (46);
-
(b) exterior doors, except for those in superstructures
and deckhouses facing life-saving appliances,
embarkation and external assembly station areas,
external stairs and open decks used for escape
routes; and
-
(c) stairway enclosure doors, glass doors and windows
(38) Except for watertight doors, weathertight doors, semi-watertight
doors, doors leading to the open deck and doors which need to be
reasonably gastight, all "A" class doors located in stairways,
public spaces and main vertical zone bulkheads in escape routes
shall be equipped with a self-closing hose port, the material,
construction and fire resistance of which shall be equivalent to the
door into which it is fitted, and the port shall be a 150
millimetres square clear opening with the door closed and shall be
inset into the lower edge of the door, opposite the door hinges or,
in the case of sliding doors, nearest the opening.
(39) Ventilation ducts passing through main vertical zone divisions must
be kept to a minimum and where it is necessary that a such a duct
passes through a main vertical zone division, a fail-safe automatic
closing fire damper shall be fitted adjacent to the division
complying with the following provisions-
-
(a) the damper shall be capable of being manually closed
from each side of the division;
-
(b) the operating position of the damper shall be readily
accessible and be marked in red light-reflecting
colour;
-
(c) the duct between the division and the damper shall be
of steel or other equivalent material and, if
necessary, insulated to comply with the requirements
of subsection (28); and
-
(d) the damper shall be fitted on at least one side of
the division with a visible indicator showing
whether the damper is in the open position.
Openings in "B" Class Divisions
(40) Doors and door frames in "B" class divisions and means of securing
them shall provide a method of closure which shall have resistance
to fire equivalent to that of the divisions, this being determined
in accordance with the Fire Test Procedures Code provided that that
ventilation openings may be permitted in the lower portion of such
doors as follows-
-
(a) where such opening is in or under a door the total
net area of any such opening or openings shall not
exceed 0.05 m2;
-
(b) alternatively, a non-combustible air balance duct
routed between the cabin and the corridor, and
located below the sanitary unit, is permitted where
the cross-sectional area of the duct does not exceed
0.05m2;
-
(c) all ventilation openings shall be fitted with a grill
made of non-combustible material;
-
(d) doors shall be non-combustible; and
-
(e) doors approved without the sill being part of the
frame, shall be installed such that the gap under
the door does not exceed 25 mm.
(41) Cabin doors in "B" class divisions shall be of a self-closing type.
Hold-back hooks are not permitted.
(42) The requirements for "B" class integrity of the outer boundaries of
a ship shall not apply to glass partitions, windows and
sidescuttles. Similarly, the requirements for "B" class integrity
shall not apply to exterior doors in superstructures and deckhouses.
The Administration may permit the use of combustible materials in
doors separating cabins from the individual interior sanitary spaces
such as showers.
(43) The following provisions apply to openings in “B” Class
Divisions-
-
(a) openings in decks not forming steps in main vertical
zones nor bounding horizontal zones shall be closed
reasonably tight and such decks shall meet the "B"
class integrity requirements in so far as is
reasonable and practicable in the opinion of the
Administration; and
-
(b) openings in corridor bulkheads of "B" class materials
shall be protected in accordance with the provisions
of subsections (8) and (9).
Windows, Sidescuttles Weathertight and Watertight Doors
(44) Windows and sidescuttles in bulkheads within accommodation and
service spaces and control stations other than those to which the
provisions of subsections (35) and (40) apply shall be so
constructed as to preserve the integrity requirements of the type of
bulkheads in which they are fitted, this being determined in
accordance with the Fire Test Procedures Code.
(45) A-class windows and sidescuttles in bulkheads separating
accommodation and service spaces and control stations from weather
shall be constructed with frames of steel or other suitable material
and the glass shall be mechanically retained. See also 2.12(22).
(46) Windows and doors (except those leading from
stairways)-facing life-saving appliances, embarkation and
assembly stations, external stairs and open decks used for
escape routes, and windows situated below survival craft,
liferaft and escape slide embarkation areas shall have the
following fire integrity:
-
(a) open decks used as embarkation and assembly
stations shall be to class “A-30” standard; and
-
(b) areas in the ship’s side situated below survival
craft launching positions, escape slide
arrangements or stowage areas for survival craft,
shall also be to class “A-30” standard; and
-
(c) where no lifeboats are fitted, areas in the ship’s
side situated below the rescue boat launching
positions, and stowage areas for rescue boats,
shall also be to class “A-30” standard; and
-
(d) open decks, including external stairs, used as
escape routes, shall be to class “A-0” standard
unless, with the conditions in subparagraph (i),
the requirements in subparagraph (ii) are complied
with:
-
(i) A fire within a space in which the
window/door is located should be assumed to result
in all the windows or doors failing in that space,
rendering the fire boundary in which they are
situated ineffective, creating a ‘failed fire
boundary’. Windows located beyond a B-Class deck
to deck boundary or higher fire rating, are
considered to be located in a separate space.
-
(ii) There must continue to be a means of
escape providing direct access to the embarkation
deck by way of external stairways/passageways,
that does not:
-
(ba) pass along a ‘failed fire
boundary’;
-
(bb) require the use of the
second means of escape required by 6.11(9) &
(11); or
-
(bc) require the escaping
person(s) to have to return along, down or up the
escape route that they have already passed.
(47) Where automatic dedicated sprinkler heads are provided for
windows or glass doors, "A-0" windows or glass doors may be
accepted as equivalent to those required under subsection
(46); provided that to be considered under this paragraph,
the sprinkler heads shall either be-
-
(a) dedicated heads located above the windows or glass
doors, and installed in addition to the
conventional ceiling sprinklers;
-
(b) conventional ceiling sprinkler heads arranged such
that the window or glass door is protected by an
average application rate of at least
5l/min/m2 and the additional window
area is included in the calculation of the area of
coverage; or
-
(c) water-mist nozzles that have been tested and
approved in accordance with the guidelines
approved by the IMO.
(48) Steel watertight doors need not be insulated.
Protection of Openings in Machinery Spaces Boundaries
(49) The provision of subsections (50) to (55) shall apply to machinery
spaces of category A and, where the Administration considers it
desirable, to other machinery spaces.
(50) The number of skylights, doors, ventilators, openings in funnels to
permit exhaust ventilation and other openings to machinery spaces
shall be reduced to a minimum consistent with the needs of
ventilation and the proper and safe working of the ship.
(51) Skylights shall be of steel and shall not contain glass panels.
(52) Means of control shall be provided for closing power-operated doors
or actuating release mechanisms on doors other than power-operated
watertight doors and such controls shall be located outside the
space served so that they will not be cut off in the event of fire
in that place.
(53) The means of control required in subsection (52) shall be situated
at one control position or grouped in as few positions as possible
to the satisfaction of the Administration and such positions shall
have safe access from the open deck.
(54) Doors, other than power-operated watertight doors, shall be so
arranged that positive closure is assured in case of fire in the
space by power-operated closing arrangements or by the provision of
self-closing doors capable of closing against an inclination of 3.5°
opposing closure, and having a fail-safe hold-back arrangement;
provided with a remotely operated release device; provided that
doors for emergency escape trunks need not be fitted with a
fail-safe hold-back facility and a remotely operated release device.
(55) Windows shall not be fitted in machinery space boundaries. However,
this does not preclude the use of glass in control rooms within the
machinery spaces.
Ventilation Systems
(56) Ventilation ducts, including single and double wall ducts, shall be
of steel or equivalent material except flexible bellows of short
length not exceeding 600 mm used for connecting fans to the ducting
in air-conditioning rooms. Unless expressly provided otherwise in
paragraph (61), any other material used in the construction of
ducts, including insulation, shall also be non-combustible. However,
short ducts, not generally exceeding 2 m in length and with a free
cross-sectional areafootnote not exceeding 0.02 m2,
need not be of steel or equivalent material, subject to the
following conditions:
-
(a) the ducts shall be made of non-combustible material,
which may be faced internally and externally with
membranes having low flame-spread characteristics
and, in each case, a calorific valuefootnote not exceeding 45
MJ/m2 of their surface area for the
thickness used;
-
(b) the ducts are only used at the end of the ventilation
device; and
-
(c) the ducts are not situated less than 600 mm, measured
along the duct, from an opening in an "A" or "B"
class division, including continuous "B" class
ceiling.
(57) The following arrangements shall be tested in accordance with the
Fire Test Procedures Code-
-
(a) fire dampers, including their relevant means of
operation; and
-
(b) duct penetrations through "A" class divisions.
However, the test is not required where steel
sleeves are directly joined to ventilation ducts by
means of riveted or screwed flanges or by welding.
(58) Fire dampers shall be easily accessible. Where they are placed
behind ceilings or linings, these ceilings or linings shall be
provided with an inspection hatch on which the identification number
of the fire damper is marked. The fire damper identification number
shall also be marked on any remote controls provided.
(59) Ventilation ducts shall be provided with hatches for inspection and
cleaning. The hatches shall be located near the fire dampers.
(60) The main inlets and outlets of ventilation systems shall be capable
of being closed from outside the spaces being ventilated. The means
of closing shall be easily accessible as well as prominently and
permanently marked and shall indicate the operating position of the
closing device.
(61) Combustible gaskets in flanged ventilation duct connections are not
permitted within 600 mm of openings in "A" or "B" class divisions
and in ducts required to be of "A" class construction.
(62) Ventilation openings or air balance ducts between two enclosed
spaces shall not be provided except as permitted by paragraph
6.7(40).
(63) The ventilation systems for machinery spaces of category A, vehicle
spaces and galleys shall, in general, be separated from each other
and from the ventilation systems serving other spaces. However, the
galley ventilation systems need not be completely separated from
other ventilation systems, but may be served by separate ducts from
a ventilation unit serving other spaces. In such a case, an
automatic fire damper shall be fitted in the galley ventilation duct
near the ventilation unit.
(64) Ducts provided for the ventilation of machinery spaces of category
A, galleys and vehicle spaces shall not pass through accommodation
spaces, service spaces, or control stations unless they comply with
paragraph (66).
(65) Ducts provided for the ventilation of accommodation spaces, service
spaces or control stations shall not pass through machinery spaces
of category A, galleys and vehicle spaces, unless they comply with
paragraph (66).
(66) As permitted by paragraphs (64) and (65) ducts shall be either:
-
(a) constructed of steel having a thickness of at least 3
mm for ducts with a free cross-sectional area of
less than 0.075 m2, at least 4 mm for
ducts with a free cross-sectional area of between
0.075 m2 and 0.45 m2, and at
least 5 mm for ducts with a free cross-sectional
area of over 0.45 m2;
-
(b) suitably supported and stiffened;
-
(c) fitted with automatic fire dampers close to the
boundaries penetrated; and
-
(d) insulated to "A-60" class standard from the
boundaries of the spaces they serve to a point at
least 5 m beyond each fire damper;
or
-
(e) constructed of steel in accordance with sub-sections
(a) and (b); and
-
(f) insulated to "A-60" class standard throughout the
spaces they pass through, except for ducts that pass
through the following spaces;
-
(iii) Sanitary and similar spaces such as;
-
(bd) Communal sanitary
facilities, showers, baths, water closets, etc.
-
(be) Small laundry rooms.
-
(bf) Indoor swimming pool area.
-
(bg) Isolated pantries containing
no cooking appliances in accommodation spaces.
-
(bh) Private sanitary facilities
shall be considered a portion of the space in
which they are located.
-
(iv) Tanks, voids and auxiliary machinery
spaces having little or no fire risk such as;
-
(bi) Water tanks forming part of
the ship’s structure.
-
(bj) Voids and cofferdams.
-
(bk) Auxiliary machinery space
which do not contain machinery having a pressure
lubrication system and where storage of
combustibles is prohibited, such as:
-
(bl) . ventilation and
air-conditioning rooms;
-
(bm) windlass room;
-
(bn) steering gear room;
-
(bo) stabilizer equipment room;
-
(bp) electrical propulsion motor
room;
-
(bq) rooms containing section
switchboards and purely electrical equipment other
than oil-filled electrical transformers (above 10
kVA);
-
(br) shaft alleys and pipe
tunnels;
-
(bs) spaces for pumps and
refrigeration machinery (not handling or using
flammable liquids).
-
(bt) Closed trunks serving the
spaces listed above.
-
(bu) Other closed trunks such as
pipe and cable trunks.
(67) For the purposes of sub-paragraphs (66)(d) and (66)(f), ducts shall
be insulated over their entire cross-sectional external surface.
Ducts that are outside but adjacent to the specified space, and
share one or more surfaces with it, shall be considered to pass
through the specified space, and shall be insulated over the surface
they share with the space for a distance of 450 mm past the
ductfootnote.
(68) Where it is necessary that a ventilation duct passes through a main
vertical zone division, an automatic fire damper shall be fitted
adjacent to the division. The damper shall also be capable of being
manually closed from each side of the division. The control location
shall be readily accessible and be clearly and prominently marked.
The duct between the division and the damper shall be constructed of
steel in accordance with sub-paragraphs (66)(a) and (66)(b) and
insulated to at least the same fire integrity as the division
penetrated. The damper shall be fitted on at least one side of the
division with a visible indicator showing the operating position of
the damper.
(69) Ducts passing through "A" class divisions shall meet the following
requirements:
-
(a) where a thin plated duct with a free cross sectional
area equal to, or less than, 0.02 m2
passes through "A" class divisions, the opening
shall be fitted with a steel sheet sleeve having a
thickness of at least 3 mm and a length of at least
200 mm, divided preferably into 100 mm on each side
of a bulkhead or, in the case of a deck, wholly laid
on the lower side of the decks penetrated;
-
(b) where ventilation ducts with a free cross-sectional
area exceeding 0.02 m2, but not more than
0.075 m2, pass through "A" class
divisions, the openings shall be lined with steel
sheet sleeves. The ducts and sleeves shall have a
thickness of at least 3 mm and a length of at least
900 mm. When passing through bulkheads, this length
shall be divided preferably into 450 mm on each side
of the bulkhead. These ducts, or sleeves lining such
ducts, shall be provided with fire insulation. The
insulation shall have at least the same fire
integrity as the division through which the duct
passes; and
-
(c) automatic fire dampers shall be fitted in all ducts
with a free cross-sectional area exceeding 0.075
m2 that pass through "A" class
divisions. Each damper shall be fitted close to the
division penetrated and the duct between the damper
and the division penetrated shall be constructed of
steel in accordance with paragraphs (66)(a) and
(66)(b). The fire damper shall operate
automatically, but shall also be capable of being
closed manually from both sides of the division. The
damper shall be fitted with a visible indicator
which shows the operating position of the damper.
Fire dampers are not required, however, where ducts
pass through spaces surrounded by "A" class
divisions, without serving those spaces, provided
those ducts have the same fire integrity as the
divisions which they penetrate. A duct of
cross-sectional area exceeding 0.075 m2
shall not be divided into smaller ducts at the
penetration of an "A" class division and then
recombined into the original duct once through the
division to avoid installing the damper required by
this provision.
(70) Ventilation ducts with a free cross-sectional area exceeding 0.02
m2 passing through "B" class bulkheads shall be
lined with steel sheet sleeves of 900 mm in length, divided
preferably into 450 mm on each side of the bulkheads unless the duct
is of steel for this length.
(71) All fire dampers shall be capable of manual operation. The dampers
shall have a direct mechanical means of release or, alternatively,
be closed by electrical, hydraulic, or pneumatic operation. All
dampers shall be manually operable from both sides of the division.
Automatic fire dampers, including those capable of remote operation,
shall have a failsafe mechanism that will close the damper in a fire
even upon loss of electrical power or hydraulic or pneumatic
pressure loss. Remotely operated fire dampers shall be capable of
being reopened manually at the damper.
(72) When passing through accommodation spaces or spaces containing
combustible materials, the exhaust ducts from galley ranges shall be
constructed in accordance with paragraphs (66)(a) and (66)(b). Each
exhaust duct shall be fitted with:
-
(a) a grease trap readily removable for cleaning;
-
(b) an automatically and remotely operated fire damper
located in the lower end of the duct at the junction
between the duct and the galley range hood and, in
addition, a remotely operated fire damper in the
upper end of the duct close to the outlet of the
duct;
-
(c) arrangements, operable from within the galley, for
shutting off the exhaust and supply fans; and
-
(d) fixed means for extinguishing a fire within the
ductfootnote.
(73) Exhaust ducts from laundries shall be fitted with:
-
(a) filters readily removable for cleaning purposes;
-
(b) a fire damper located in the lower end of the duct
which is automatically and remotely operated;
-
(c) remote-control arrangements for shutting off the
exhaust fans and supply fans from within the space
and for operating the fire damper mentioned in (b);
and
-
(d) suitably located hatches for inspection and cleaning.
Construction and Arrangement of Steam Room
(74) Construction and Arrangement of Steam Rooms shall meet the following
requirements:
-
(a) The perimeter of the steam room may include changing
rooms, showers and toilets.
-
(b) Bathrooms with direct access to suite may be
considered as part of it. In such cases, the door
between suite and the bathroom need not comply with
fire safety requirements.
-
(c) If a steam generator of more than 5 kW is contained
within the perimeter, the suite boundary should be
constructed to an A-0 standard. If a steam generator
of more than 5 kW is not contained within the
perimeter the steam generator should be protected by
A-0 standard divisions, and pipes leading to the
discharge nozzles should be lagged.
-
(d) All spaces within the perimeter are to be protected
by a fire detection and alarm system.