The following minimum level of maintenance and inspections should be carried
out in accordance with the system manufacturer's instructions and safety
precautions:
-
.1 the boundaries of the protected space should
be visually inspected to confirm that no modifications have been made
to the enclosure that have created uncloseable openings that would
render the system ineffective;
-
.2 all storage containers should be visually inspected
for any signs of damage, rust or loose mounting hardware. Cylinders
that are leaking, corroded, dented or bulging should be hydrostatically
retested or replaced;
-
.3 system piping should be visually inspected to
check for damage, loose supports and corrosion. Nozzles should be inspected to
ensure they have not been obstructed by the storage of spare parts or a new
installation of structure or machinery;
-
.4 the manifold should be inspected to verify that
all flexible discharge hoses and fittings are properly tightened; and
-
.5 all entrance doors to the protected space should
close properly and should have warning signs, which indicate that the space is
protected by a fixed carbon dioxide system and that personnel should evacuate
immediately if the alarms sound. All remote releasing controls should be checked
for clear operating instructions and indication as to the space served.