9.9.1 In spaces where main or auxiliary oil-fired boilers
and other fired processes of equivalent thermal rating are situated, or in spaces
containing oil fuel units or settling tanks, the unit should be provided with the
following:
-
.1 One of the following fixed fire-extinguishing
systems complying with SOLAS regulation
II-2/10.4:
-
.1.1 a fixed pressure water-spraying system;
-
.1.2 a fixed gas fire-extinguishing system;
-
.1.3 a fixed high-expansion foam installation.
Where the machinery space and spaces containing fired processes
are not entirely separate, or if fuel oil can drain from the latter
spaces into the machinery space, the combined machinery space and
fired process space should be considered as one compartment.
-
.2 At least two approved portable foam extinguishers
or equivalent in each space containing a fired process and each space in which a
part of the oil fuel installation is situated. In addition, at least one
extinguisher of the same description with a capacity of 9 l for
each burner, whereby the total capacity of the additional extinguisher or
extinguishers need not exceed 45 l for any one space.
-
.3 A receptacle containing sand, sawdust impregnated
with soda, or other approved dry material in such quantity as may
be required by the Administration. An approved portable extinguisher
may be provided as an alternative.
9.9.2 Spaces containing internal combustion machinery used
either for main propulsion or for other purposes, when such machinery has a total power
output of not less than 750 kW, should be provided with the following arrangements:
-
.1 one of the fixed arrangements required by
paragraph 9.9.1.1; and
-
.2 one approved foam-type extinguisher of not less
than 45 l capacity or equivalent in every engine space and one
approved portable foam extinguisher for each 750 kW of engine power output or part
thereof. The total number of portable extinguishers so supplied should be not less
than two and need not exceed six.
9.9.3 The Administration should give special consideration
to the fire-extinguishing arrangements to be provided in spaces not fitted with fixed
fire-extinguishing installations containing steam turbines which are separated from
boiler rooms by watertight bulkheads.
9.9.4 Where, in the opinion of the Administration, a fire
hazard exists in any machinery space for which no specific provisions for
fire-extinguishing appliances are prescribed in paragraphs 9.9.1 to 9.9.3, there should
be provided in, or adjacent to, that space a number of approved portable fire
extinguishers or other means of fire extinction to the satisfaction of the
Administration.