14.2.2.1 The perimeter of the thermal suite may
include changing rooms, showers and toilets.
14.2.2.2 Bathrooms with direct access to suite
may be considered as part of it. In such cases, the door between suite
and the bathroom need not comply with fire safety requirements.
14.2.2.3 If the steam generator is contained within
the perimeter, the suite boundary should be constructed to an A-0
standard, or B-0 for Short Range Yachts. If the steam generator is
not contained within the perimeter then the boundaries of the space
should be constructed of B-0 class divisions, and the steam generator
should be protected by A-0 standard divisions, or B-0 for Short Range
Yachts.
14.2.2.4 If a suite arrangement contains a sauna
then the requirements contained in 14.2.1 are applicable, regardless
of the steam generator location.
14.2.2.5 All spaces within the perimeter are to
be protected by a fire detection and alarm system and an automatic
sprinkler.