Location of portable fire extinguishers including
suitability and capacity
Fire extinguishers in special-category spaces should be
suitable for A and B class fires. The extinguishers should have a
capacity of 12 kg dry powder or equivalent.
Weight and capacity of fire extinguishers
1 The weight of portable fire extinguishers should
not exceed 23 kg.
2 Each powder or carbon dioxide extinguisher should
have a capacity of at least 5 kg, and each foam extinguisher a capacity
of at least 9 l.