3.2.1 A remotely operated cargo vapour shutoff
valve should be provided in close proximity to each terminal vapour
connection. This valve should meet the following:
-
.1 be located between any point where inerting,
enriching, or diluting gas is introduced into the vapour collection
line and the terminal vapour connection;
-
.2 be capable of manual operation or manual activation;
-
.3 have valve operating position readily determined
visually; and
-
.4 be resistant to fire.
3.2.2 The end of each vapour collection pipe,
vapour collection hose, or vapour collection arm should be readily
identifiable to prevent misconnection.
3.2.3 Each terminal vapour connection flange should
conform to the provisions referred to in section 2.3.3 of these standards.
3.2.4 Each vapour collection hose or arm should
meet the following:
-
.1 be suitable for the intended service;
-
.2 be electrically continuous; and
-
.3 have an extra hole in each flange in accordance
with the applicable industry standardfootnote.
3.2.5 The terminal vapour connection should be
electrically insulated from the tanker vapour connection by the use
of an insulating flange or a single section of insulating hose.