5.5.1.1 Every cargo tank and piping system shall
be fitted with manually operated valves for isolation purposes as
specified in this section.
5.5.1.2 In addition, remotely operated valves
shall also be fitted, as appropriate, as part of the emergency shutdown
(ESD) system the purpose of which is to stop cargo flow or leakage
in the event of an emergency when cargo liquid or vapour transfer
is in progress. The ESD system is intended to return the cargo system
to a safe static condition so that any remedial action can be taken.
Due regard shall be given in the design of the ESD system to avoid
the generation of surge pressures within the cargo transfer pipework.
The equipment to be shut down on ESD activation includes manifold
valves during loading or discharge, any pump or compressor, etc.,
transferring cargo internally or externally (e.g. to shore or another
ship/barge) and cargo tank valves, if the MARVS exceeds 0.07 MPa.
5.5.2
Cargo tank connections
5.5.2.1 All liquid and vapour connections, except
for safety relief valves and liquid level gauging devices, shall have
shutoff valves located as close to the tank as practicable. These
valves shall provide full closure and shall be capable of local manual
operation. They may also be capable of remote operation.
5.5.2.2 For cargo tanks with a MARVS exceeding
0.07 MPa gauge, the above connections shall also be equipped with
remotely controlled ESD valves. These valves shall be located as close
to the tank as practicable. A single valve may be substituted for
the two separate valves, provided the valve complies with the requirements
of 18.10.2 and provides full closure of the line.
5.5.3
Cargo manifold connections
5.5.3.1 One remotely controlled ESD valve shall
be provided at each cargo transfer connection in use to stop liquid
and vapour transfer to or from the ship. Transfer connections not
in use shall be isolated with suitable blank flanges.
5.5.3.2 If the cargo tank MARVS exceeds 0.07 MPa,
an additional manual valve shall be provided for each transfer connection
in use, and may be inboard or outboard of the ESD valve to suit the
ship's design.
5.5.4 Excess flow valves may be used in lieu of
ESD valves, if the diameter of the protected pipe does not exceed
50 mm. Excess flow valves shall close automatically at the rated closing
flow of vapour or liquid as specified by the manufacturer. The piping
including fittings, valves and appurtenances protected by an excess
flow valve shall have a capacity greater than the rated closing flow
of the excess flow valve. Excess flow valves may be designed with
a bypass not exceeding the area of a 1 mm diameter circular opening
to allow equalization of pressure after a shutdown activation.
5.5.5 Cargo tank connections for gauging or measuring
devices need not be equipped with excess flow valves or ESD valves,
provided that the devices are constructed so that the outward flow
of tank contents cannot exceed that passed by a 1.5 mm diameter circular
hole.
5.5.6 All pipelines or components which may be
isolated in a liquid full condition shall be protected with relief
valves for thermal expansion and evaporation.
5.5.7 All pipelines or components which may be
isolated automatically due to a fire with a liquid volume of more
than 0.05 m3 entrapped shall be provided with PRVs sized
for a fire condition.