8.4.1
Sizing of pressure relief valves
PRVs shall have a combined relieving capacity for each cargo
tank to discharge the greater of the following, with not more than
a 20% rise in cargo tank pressure above the MARVS:
8.4.1.1 The maximum capacity of the cargo tank
inerting system, if the maximum attainable working pressure of the
cargo tank inerting system exceeds the MARVS of the cargo tanks; or
8.4.1.2 Vapours generated under fire exposure
computed using the following formula:
where:
Q
|
= |
minimum
required rate of discharge of air at standard conditions of 273.15
Kelvin (K) and 0.1013 MPa; |
F
|
= |
fire
exposure factor for different cargo types as follows: |
-
- 1 for tanks without insulation located on deck;
-
- 0.5 for tanks above the deck, when insulation is approved
by the Administration. Approval will be based on the use of a fireproofing
material, the thermal conductance
-
- 0.5 for uninsulated independent tanks installed in holds;
-
– 0.2 for insulated independent tanks in holds (or
uninsulated independent tanks in insulated holds);
-
- 0.1 for insulated independent tanks in inerted holds (or
uninsulated independent tanks in inerted, insulated holds);
-
- 0.1 for membrane and semi-membrane tanks. For independent
tanks partly protruding through the weather decks, the fire exposure
factor shall be determined on the basis of the surface areas above
and below deck.
G
|
= |
gas
factor according to formula: |
A
|
= |
external
surface area of the tank (m2), as defined in 1.2.14, for
different tank types, as shown in figure 8.1.
|
8.4.1.3 The required mass flow of air at relieving
conditions is given by the formula:
where:
density of air(ρair
)
|
= |
1.293 kg/m3 (air at 273.15 K, 0.1013
MPa).
|
8.4.2
Sizing of vent pipe system
Pressure losses upstream and downstream of the PRVs shall
be taken into account when determining their size to ensure the flow
capacity required by 8.4.1.
8.4.3
Upstream pressure losses
8.4.3.1 The pressure drop in the vent line from
the tank to the PRV inlet shall not exceed 3% of the valve set pressure
at the calculated flow rate, in accordance with 8.4.1.
8.4.3.2 Pilot-operated PRVs shall be unaffected
by inlet pipe pressure losses when the pilot senses directly from
the tank dome.
8.4.3.3 Pressure losses in remotely sensed pilot
lines shall be considered for flowing type pilots.
8.4.4
Downstream pressure losses
8.4.4.1 Where common vent headers and vent masts
are fitted, calculations shall include flow from all attached PRVs.
8.4.4.2 The built-up back pressure in the vent
piping from the PRV outlet to the location of discharge to the atmosphere,
and including any vent pipe interconnections that join other tanks,
shall not exceed the following values:
-
.1 for unbalanced PRVs: 10% of MARVS;
-
.2 for balanced PRVs: 30% of MARVS; and
-
.3 for pilot operated PRVs: 50% of MARVS.
Alternative values provided by the PRV manufacturer may
be accepted.
8.4.5 To ensure stable PRV operation, the blow-down
shall not be less than the sum of the inlet pressure loss and 0.02
MARVS at the rated capacity.