A water mist nozzle should show no evidence of clogging
during 30 min of continuous flow at rated working pressure using water
that has been contaminated in accordance with 5.21.3. Following the 30 min of
flow, the water flow at rated pressure of the nozzle and strainer
or filter should be within ±10% of the value obtained prior
to conducting the clogging test.