3.6.1 Access between hazardous area on the open weather
deck and non-hazardous spaces shall be by means of an airlock. This shall consist of two
self-closing, substantially gastight, steel doors without any holding back arrangements,
capable of maintaining the overpressure, at least 1.5 m but no more than 2.5 m apart.
The airlock space shall be artificially ventilated from a non-hazardous area and
maintained at an overpressure to the hazardous area on the weather deck.
3.6.2 Where spaces are protected by pressurization, the
ventilation shall be designed and installed in accordance with recognized standardsfootnote.
3.6.3 An audible and visible alarm system to give a warning
on both sides of the airlock shall be provided. The visible alarm shall indicate if one
door is open. The audible alarm shall sound if doors on both sides of the air lock are
moved from the closed positions.
3.6.4 In ships carrying flammable products, electrical
equipment that is located in spaces protected by airlocks and not of the certified safe
type, shall be de-energized in case of loss of overpressure in the space.
3.6.5 Electrical equipment for manoeuvring, anchoring and
mooring, as well as emergency fire pumps that are located in spaces protected by
airlocks, shall be of a certified safe type.
3.6.6 The airlock space shall be monitored for cargo
vapours (see 13.6.2).
3.6.7 Subject to the requirements of the International
Convention on Load Lines in force, the door sill shall not be less than 300 mm in
height.