1.1 These standards should be used when applying Regulation II-2/28.1.5.1 of the 1974 SOLAS
Convention as amended by Resolution MSC.27(61).
1.2 It should be recognized that the evacuation
routes to the embarkation deck may include a muster station. In this
case consideration should be given to the fire-protection requirements
and sizing of corridors and doors from the stairway enclosure to the
muster station and from the muster station to the embarkation deck
using these guidelines noting that evacuation of persons from muster
stations to embarkation positions will be carried out in small controlled
groups.
1.3 It is the intention that the calculation method
should consider evacuation from enclosed spaces within each main vertical
zone individually and take into account all of the persons using the
stairway enclosures in each zone, even if they enter that stairway
from another main vertical zone.
1.4 For each main vertical zone the calculation
should be completed for the night time (case 1) and day time (case
2) and the largest dimension from either case used for determining
the stairway width for each deck under consideration.
1.5 The calculation method determines the stairway
width at each deck level taking into account the three consecutive
stairways leading into the stairway under consideration.