16.4.1.1 The requirements of this section shall
apply to gas fuel supply piping outside of the cargo area. Fuel piping
shall not pass through accommodation spaces, service spaces, electrical
equipment rooms or control stations. The routeing of the pipeline
shall take into account potential hazards, due to mechanical damage,
in areas such as stores or machinery handling areas.
16.4.1.2 Provision shall be made for inerting
and gas-freeing that portion of the gas fuel piping systems located
in the machinery space.
Continuous monitoring and alarms shall be provided to indicate
a leak in the piping system in enclosed spaces and shut down the relevant
gas fuel supply.
16.4.3
Routeing of fuel supply pipes
Fuel piping may pass through or extend into enclosed spaces
other than those mentioned in 16.4.1, provided it fulfils one of the
following conditions:
-
.1 it is of a double-wall design with the space
between the concentric pipes pressurized with inert gas at a pressure
greater than the gas fuel pressure. The master gas fuel valve, as
required by 16.4.6, closes automatically upon loss of inert gas pressure;
or
-
.2 it is installed in a pipe or duct equipped
with mechanical exhaust ventilation having a capacity of at least
30 air changes per hour and is arranged to maintain a pressure less
than the atmospheric pressure. The mechanical ventilation is in accordance
with chapter 12, as applicable. The ventilation is always in operation
when there is fuel in the piping and the master gas fuel valve, as
required by 16.4.6, closes automatically if the required air flow
is not established and maintained by the exhaust ventilation system.
The inlet or the duct may be from a non-hazardous machinery space,
and the ventilation outlet is in a safe location.
16.4.4
Requirements for gas fuel with
pressure greater than 1 MPa
16.4.4.1 Fuel delivery lines between the high-pressure
fuel pumps/compressors and consumers shall be protected with a double-walled
piping system capable of containing a high pressure line failure,
taking into account the effects of both pressure and low temperature.
A single-walled pipe in the cargo area up to the isolating valve(s)
required by 16.4.6 is acceptable.
16.4.4.2 The arrangement in 16.4.3.2 may also
be acceptable providing the pipe or trunk is capable of containing
a high pressure line failure, according to the requirements of 16.4.7
and taking into account the effects of both pressure and possible
low temperature and providing both inlet and exhaust of the outer
pipe or trunk are in the cargo area.
16.4.5
Gas consumer isolation
The supply piping of each gas consumer unit shall be provided
with gas fuel isolation by automatic double block and bleed, vented
to a safe location, under both normal and emergency operation. The
automatic valves shall be arranged to fail to the closed position
on loss of actuating power. In a space containing multiple consumers,
the shutdown of one shall not affect the gas supply to the others.
16.4.6
Spaces containing gas consumers
16.4.6.1 It shall be possible to isolate the gas
fuel supply to each individual space containing a gas consumer(s)
or through which fuel gas supply piping is run, with an individual
master valve, which is located within the cargo area. The isolation
of gas fuel supply to a space shall not affect the gas supply to other
spaces containing gas consumers if they are located in two or more
spaces, and it shall not cause loss of propulsion or electrical power.
16.4.6.2 If the double barrier around the gas
supply system is not continuous due to air inlets or other openings,
or if there is any point where single failure will cause leakage into
the space, the individual master valve for the space shall operate
under the following circumstances:
16.4.6.3 If the double barrier around the gas
supply system is continuous, an individual master valve located in
the cargo area may be provided for each gas consumer inside the space.
The individual master valve shall operate under the following circumstances:
16.4.7
Piping and ducting construction
Gas fuel piping in machinery spaces shall comply with 5.1
to 5.9, as applicable. The piping shall, as far as practicable, have
welded joints. Those parts of the gas fuel piping that are not enclosed
in a ventilated pipe or duct according to 16.4.3, and are on the weather
decks outside the cargo area, shall have full penetration butt-welded
joints and shall be fully radiographed.
Gas detection systems provided in accordance with the requirements
of this chapter shall activate the alarm at 30% LFL and shut down
the master gas fuel valve required by 16.4.6 at not more than 60%
LFL (see 13.6.17).