9.5.1 The equipment shall be capable of producing
inert gas with an oxygen content at no time greater than 5% by volume,
subject to the special requirements of chapter 17. A continuous-reading
oxygen content meter shall be fitted to the inert gas supply from
the equipment and shall be fitted with an alarm set at a maximum of
5% oxygen content by volume, subject to the requirements of chapter
17.
9.5.2 An inert gas system shall have pressure
controls and monitoring arrangements appropriate to the cargo containment
system.
9.5.3 Spaces containing inert gas generation plants
shall have no direct access to accommodation spaces, service spaces
or control stations, but may be located in machinery spaces. Inert
gas piping shall not pass through accommodation spaces, service spaces
or control stations.
9.5.4 Combustion equipment for generating inert
gas shall not be located within the cargo area. Special consideration
may be given to the location of inert gas generating equipment using
a catalytic combustion process.