The minimum flow rate of each type of hand hose line nozzle
should be at least 3.5 kg/s and each type monitor should be at least
10 kg/s. The minimum flow rate should be determined based on the average
of three discharge tests. The tests should be conducted with the nozzle/monitor
discharged for at least 30 s. The fixed dry chemical powder unit should
be placed on a load cell or weighed before and after testing to determine
the quantity of medium discharged during the test.