4.1.2 Equipment used in fresh water systems is to be provided with local control and
                                 monitoring arrangements.
                              
                              
                              
                            
                           
                           
                           
                              
                              
                              4.1.3 Where isolation of equipment or systems can be carried out, manual or automatic means
                                 of indicating the status of isolation is to be provided at all positions where the
                                 equipment and system can be operated and monitored.
                              
                              
                              
                            
                           
                           
                           
                              
                              
                              4.1.4 Instrumentation to indicate the operational status of running equipment and of any
                                 standby equipment is to be provided locally and at each control station.
                              
                              
                              
                            
                           
                           
                           
                              
                              
                              4.1.5 All pumps are to be provided with an indication of discharge pressure and a low
                                 discharge pressure alarm at each control station from which the pumps can be
                                 operated.
                              
                              
                              
                            
                           
                           
                           
                              
                              
                              4.1.6 Sea water desalination plant instrumentation is to include, as a minimum, salinity
                                 indication and a high salinity alarm of the desalinated water at the plant and at
                                 each control station.
                              
                              
                              
                            
                           
                           
                           
                              
                              
                              4.1.7 Arrangements are to be made to automatically divert any water that is above the
                                 specified salinity limit from distribution into the on-specification fresh water
                                 storage system.
                              
                              
                              
                            
                           
                           
                           
                              
                              
                              4.1.8 Sea water desalination plants using reverse osmosis are to be provided with automatic
                                 means of sterilising the desalinated water downstream of the plant.
                              
                              
                              
                            
                           
                           
                           
                              
                              
                              4.1.9 Calorifiers are to be provided with a means of indicating and controlling the outlet
                                 temperature of fresh water to distribution systems. Low and high temperature alarms
                                 are to be provided in the hot water distribution system at each control station.